Setting the LIS-SV

This section supplements the “LIS-SV” product manual. The parameters described here are only available if the LIS-SV is used in an ABULiner control unit.

Overview of the 'ABULiner' parameter level

The following parameters can be set in the 'ABULiner' parameter level of the LIS-SV.

Parameter

Designation

See

5.10

Calling up the parameter level

Accessing the 'ABULiner' parameter level

5.11

Activating the LIS-SV for the ABULiner

Activating/deactivating the LIS-SV for the ABULiner

5.11

Setting the gear ratio

Setting the gear ratio

5.12

Activating double lifting speed

Activating double lifting speed on the LIS-SV

5.14

Setting the run-on time of the auxiliary fan

Setting the run-on time of the auxiliary fan

Warnung stürzende Last

Danger during setting work!

During setting work on the LIS-SV, monitoring of the wire rope hoist is switched off. This means the wire rope hoist cannot be monitored for excess load, among other things.  This means the wire rope hoist cannot be monitored for excess load, among other things.

This in turn means the load could fall and kill or injure people!

Do not use the crane for normal work during setting work, and only lift loads very carefully for test purposes!

Accessing the 'ABULiner' parameter level

All LIS-SV parameters which are important for the ABULiner are combined in a separate parameter level, which is shown as a submenu.

xh-39.0 driver

*    Move the load hook out of the limit switch range (up or down).

During parameter setting, the load hook must not be within the limit switch range.

*    Open the menu of the LIS-SV. See the documentation “Load indicator system LIS-SV”.

xh-39.0 driver

Enter button

Arrow buttons

*    Select parameter 5.10.

*    Press ENTER.

●   The 'ABULiner' parameter level is activated.

●   Parameter 5.11 is displayed.

Exiting the 'ABULiner' parameter level

xh-39.0 driver

Enter button

Arrow buttons

*    Select parameter 5.99.

*    Press ENTER.

●   The previous parameter level is reactivated.

●   Parameter 5.10 is displayed.

Activating/deactivating the LIS-SV for the ABULiner

The LIS-SV is automatically activated for the ABULiner if a value is entered for the parameter 5.11.

In the ABULiner mode (a value is set for parameter 5.11):

─     The LIS-SV can monitor the total load for a maximum of two wire rope hoists.

─     Input F3 (normally used for measuring the load of wire rope hoist 3) now serves in monitoring the current rotational frequency of the hoist motor.

─     A value can be entered for parameter 3.0 (maximum load capacity of wire rope hoist 3). If a value is entered for this, parameter 5.11 cannot be set.

─     This interlocking thus excludes an incorrect setting.

─     The load-controlled switching point at output TxD of the LIS-SV cannot be used.

─     Parameter 4.5 (setting for load-controlled switching point) is not available.

In the normal mode (no value is set for parameter 5.11):

─     Operation of the ABULiner Lifting/Lowering unit is not possible.

─     The LIS-SV can monitor the total load for up to three wire rope hoists.

─     Input F3 serves in measuring the load of a third wire rope hoist.

─     A value can be entered for parameter 5.11 (gear ratio). If a value is entered for this, parameter 3.0 cannot be set.

─     This interlocking thus excludes an incorrect setting.

─     The load-controlled switching point at output TxD of the LIS-SV can be used.

─     Parameter 4.5 (setting for load-controlled switching point) can be used.

Setting the gear ratio

The LIS-SV uses the signal of the encoder and the gear ratio of the hoisting gear to calculate the hook travel distance, the maximum distance in the limit switch range and the current rotational frequency of the hoist motor. The gear ratio must be set on the machine.

xh-39.0 driver

Cable speed

*    Read off the type designation at the type plate of the wire rope hoist.

*    Read off the cable speed.

*    From this table, select the gear ratio that matches the cable speed.

Cable speed

Hoist motor GM

32 m/min at 50 Hz
38 m/min at 60 Hz

25 m/min at 50 Hz
30 m/min at 60 Hz

20 m/min at 50 Hz
24 m/min at 60 Hz

16 m/min at 50 Hz
19 m/min at 60 Hz

800.4

50.01

63.49

77.77

98.16

800.5

47.03

60.04

74.66

95.03

1000.6

54.43

68.91

84.00

105.1

1000.7

54.60

68.06

81.45

104.6

2000.3

58.22

74.23

91.19

118.4

3000.4

73.61

93.92

118.4

152.9

5000.3

85.14

109.3

132.8

169.0

5000.4

80.20

104.9

127.7

160.6

6000.3

94.69

118.5

149.6

182.7

7000.1

118.0

148.3

182.6

232.0

Table: Gear ratios (numerical values) depending on hoist motor (lines) and cable speeds (columns) at 50 and 60 Hz.

xh-39.0 driver

Enter button

Arrow buttons

*    Move the load hook out of the limit switch range (up or down).

During parameter setting, the load hook must not be within the limit switch range.

*    Select parameter 5.11.

*    Press ENTER.

●   The set value is displayed.

If the value is 0.00, the function is deactivated.

●   Hold ENTER pressed.

●   CODE is displayed.

*    Hold ENTER pressed.

xh-39.0 driver

Enter button

Arrow buttons

*    Enter the code 1443.

*    Press ENTER briefly.

xh-39.0 driver

Enter button

Arrow buttons

*    Set the value from the table.

If the display ‘0.00’ cannot be changed, a value is set in parameter 3.0.  In this case, set the value to zero first.

*    Press ENTER briefly.

Xh-39.0 Driver » | EXTENDED |

Are you having trouble with a specific during the installation of your XH-39.0 driver?

: These often indicate a physical seating issue. If using the PCI card version, try moving it to a different slot or cleaning the gold contacts with isopropyl alcohol. Driver Incompatibility : If an installer fails, try installing the driver in Compatibility Mode

Hardware connectivity relies entirely on stable software communication. When dealing with specialized controller boards, interface adapters, or embedded USB-to-serial chips, the is the core component that bridges your physical hardware with your operating system. Without the correct driver configuration, devices may fail to initialize, drop connections, or show up as an "Unknown Device" in your system manager.

: Ideal for connecting peripherals like keyboards, mice, printers, and external storage to systems with insufficient built-in ports. Driver Information & Installation xh-39.0 driver

Driver management is becoming increasingly automated. Operating systems are becoming smarter at downloading and installing drivers in the background. New formats like Microsoft's "Windows Driver Package" and universal drivers aim to reduce compatibility issues.

If the card is not recognized, you may need to manually point Windows to the "XH-39.0" folder on the provided disc using the "Browse my computer for driver software" option in Device Manager. ⚠️ Security Note

Understanding the "XH-39.0" Confusion: Driver Code vs. Driver Version Are you having trouble with a specific during

Secure the official XH-39.0 driver zip file from your hardware manufacturer’s support portal.

⭐️⭐️⭐️⭐️⭐️ PC Software Driver CD XH-39.0 - eBay UK

After the restart, Windows will rebuild these registry entries automatically, and your USB ports should start working again. Driver Incompatibility : If an installer fails, try

Navigate to your downloaded XH-39.0 Linux source directory:

Installing the XH-39.0 driver is a straightforward process that can be completed in a few steps:

This is the most common fix and often resolves the issue by forcing Windows to reinstall the driver from its cache, potentially repairing any corruption.

Always download driver files directly from the official manufacturer support portal. Avoid third-party "driver pack" websites, which often bundle malicious adware or outdated files with the package. Search for the specific XH-39.0 package corresponding to your exact operating system architecture (32-bit or 64-bit). Step 3: Executing the Installation

A common "deep" technical issue involves the USB Selective Suspend setting. If a USB device stops responding, disabling "USB Suspend" in advanced power settings can often fix connection drops.

Only for auxiliary fans

Setting the run-on time of the auxiliary fan

The auxiliary fan of the hoist motor continues to run for several minutes after the lifting or lowering. This ensures that the hoist motor is adequately cooled even at slow lifting speeds. The run-on time can be adjusted.

xh-39.0 driver

Enter button

Arrow buttons

*    Move the load hook out of the limit switch range (up or down).

During parameter setting, the load hook must not be within the limit switch range.

*    Select parameter 5.14.

*    Press ENTER.

●   The set value is displayed.

xh-39.0 driver

Enter button

*    Set the value to between 3 and 10 minutes using the arrow buttons.

*    Press ENTER.